Kyoritsu KEW 5410 RCD Tester

Kyoritsu KEW 5410 RCD Tester

Kyoritsu KEW 5410 RCD Tester

High precision RCD testing for industrial electrical safety

Product Overview

Kyoritsu KEW 5410 RCD Tester Price in Bangladesh

Kyoritsu KEW 5410 RCD Tester Price in Bangladesh is widely searched by electricians and industrial maintenance professionals who need a reliable and accurate solution for testing residual current devices in electrical systems. Kyoritsu KEW 5410 RCD Tester Price in Bangladesh represents a professional grade instrument designed to ensure electrical safety and proper operation of protective devices in residential, commercial, and industrial installations.

The Kyoritsu KEW 5410 RCD Tester is designed to measure RCD tripping time and trip current with high accuracy. It helps technicians verify whether protective devices are functioning correctly and responding within safe limits. This ensures that electrical systems are properly protected against leakage faults, reducing the risk of electrical hazards and equipment damage.

This device is built with advanced Japanese engineering, offering stable performance and reliable measurement results even in demanding environments. It supports multiple testing modes, allowing users to perform comprehensive evaluations of different types of RCDs used in modern electrical systems. The tester is suitable for fieldwork as well as professional maintenance operations.

The durable construction of the Kyoritsu KEW 5410 ensures long lasting performance, making it ideal for industrial use. It is designed to withstand tough working conditions such as factories, construction sites, and power distribution environments. The clear display and user friendly interface make it easy to operate, even during complex testing tasks.

Overall, the Kyoritsu KEW 5410 RCD Tester is a trusted tool for electrical professionals who require accurate, safe, and efficient RCD testing. It combines precision, durability, and advanced functionality, making it an essential instrument for ensuring electrical system safety and compliance.

Key Features: Kyoritsu KEW 5410 RCD Testers

• Measurement of RCD trip time
 Conducting testing of rated residual non-operating currents at
 × 1/2 Range, measuring RCD trip time at × 1 and × 5 Ranges.
• Measurement of the trip out current
 Measuring trip out current by varying current automatically.
• Remote Test
 Enabling a user to hold the Test Leads with his both hands
 by locking the Test Button. Measurement will automatically
 start when the mains voltage is detected.
• Voltage Measurement
 Carrying out a constant measurement of voltage in the
 stand-by mode at each Range.
• Auto-detection of Contact voltage
 Detecting the voltage to earth of Earth electrodes or
 Protective conductors during RCD test - when applying
 test currents - at measurement using EARTH in order to
 prevent electrical shocks caused by the damaged earth.
 Measurement will be ceased at AC50V or more.
• Dust- and Water-proof
 Dust- and Water-proof construction
 (designed to IEC 60529 IP54).
• Backlight
 Facilitating working at dimly illuminated locations.

Specifications

Specifications: Kyoritsu KEW 5410 RCD Testers

Range × 5 × 1 × 1/2 AUTO RAMP(mA)
Rated Voltage 100V±10%
200V-10%~+32%
400V±10%
50/60Hz
Test current 15/30/50/100mA 15/30/50/100/200/500mA 15/30/50/100/200/500mA
Measuring range Testing time
0ms~200ms
Testing time
0ms~2000ms
Testing time
0ms~2000ms
40% - 110% of lΔn
(goes up by 5%)
Testing time
300ms × 15steps
Accuracy
(Trip Time)
1%rdg±3dgt 1%rdg±3dgt 1%rdg±3dgt Test Current at each step
-4%~+4%

Accuracy
(Trip Time)

+2%~+8%dgt +2%~+8%dgt -8%~-2%dgt

Voltage Measurement

Measuring range 80V~450V 50/60Hz
Accuracy 2%rdg±4dgt
Applicable standards IEC 61010-1 Pollution degree2 CAT III 300V / CAT II 400V
IEC 61010-031
IEC 61557-1, 6
IEC 60529 (IP54)
Display 1999 counts (3 1/2digits), Large LCD
Operating temperature & humidity range 0ºC - 40ºC, relative humidity 85% (no condensation)
Storage temperature & humidity range -20ºC - 60ºC, relative humidity 85% (no condensation)
Insulation resistance 50MΩ or more / 1000V (between electrical circuit and enclosure)
Sleep Function (1)Automatically enters Sleep mode in 3 minutes after the last switch operation (current consumption 75µA). This function doesn't work at voltage measurements. To exit from the Sleep mode, set the Function switch to OFF position once, and re-set it to the Range at which a measurement to be conducted.
(2) Backlight turns off in 1 minute after it lights up.
Power source DC 12V / R6(AA)(1.5V) × 8
Dimensions 167(L)×186(W)×89(D)mm
Weight Approx. 965g (including batteries)
Possible number of Measurements 1200 times or more
(measure every 30 seconds at ×1/2 Range, lΔn=100mA)
Included Accessories 7128A (Test leads)
7129A (Test lead with alligator clip)
8017 (Long pin) × 2
Cord case, 9121 (Shoulder strap), Instruction manual,

Interested in this product?

Contact us via WhatsApp for more information, pricing, or to place an order.

Contact Us on WhatsApp
WhatsApp Chat