Fluke 435-II Power Quality and Energy Analyzers

  • Home
  • Products
  • Fluke 435-II Power Quality and Energy Analyzers
Fluke 435-II Power Quality and Energy Analyzers

Fluke 435-II Power Quality and Energy Analyzers

Advanced Power Quality and Energy Analysis for Professionals

Product Overview

Fluke 435-II Power Quality and Energy Analyzers Price in Bangladesh

Fluke 435-II Power Quality and Energy Analyzers is a high end industrial grade electrical testing instrument designed for advanced power quality monitoring, energy analysis, and system diagnostics and the Fluke 435-II Power Quality and Energy Analyzers Price in Bangladesh is widely searched by engineers and industrial professionals who require accurate and reliable electrical system evaluation tools. It is commonly used in power plants, manufacturing industries, substations, and large commercial facilities.

This advanced analyzer provides comprehensive measurement of voltage, current, power, harmonics, energy consumption, and power quality parameters, allowing engineers to detect issues such as voltage dips, swells, transients, unbalance, and waveform distortion. It helps in identifying electrical inefficiencies and improving overall system performance.

The device is engineered with high precision measurement technology that ensures stable and accurate real time data acquisition. It supports detailed waveform capture and event logging, enabling users to analyze complex electrical disturbances and perform in depth power system studies. Its intuitive interface allows efficient operation in field conditions.

Built with a rugged industrial design, the Fluke 435-II is suitable for harsh working environments and long term field use. It provides reliable performance during continuous monitoring tasks and supports advanced troubleshooting in critical electrical systems. The durable construction ensures long lasting operation in demanding industrial applications.

With its advanced energy analysis capabilities, the Fluke 435-II Power Quality and Energy Analyzers is an essential tool for professionals who need precise power system evaluation, energy optimization, and preventive maintenance solutions in industrial and commercial environments.

Key features: Fluke 435-II Power Quality and Energy Analyzers

Analyze power quality issues, calculate the costs of wasted energy and prevent downtime with the Fluke 434-II Energy Analyzer and Fluke 435-II Power Quality and Energy Analyzer.

  • Advanced power quality health—At-a-glance power quality health data in real-time so you can make better maintenance decisions
  • Energy loss calculator—Discover the costs of energy loss specifically caused by poor power quality
  • Highest safety rating in the industry—CAT III 1000 V / CAT IV 600 V
Specifications

Specifications: Fluke 434-II and 435-II Power Quality and Energy Analyzers

Volt
  Model Measurement Range Resolution Accuracy
Vrms (AC + DC) 434-II 1 V to 1000 V phase to neutral 0.1 V ±0.1% of nominal voltage1
435-II 1 V to 1000 V phase to neutral 0.01 V ±0.1% of nominal voltage1
Vpk 1 Vpk to 1400 Vpk 1 V 5% of nominal voltage
Voltage Crest Factor (CF) 1.0 > 2.8 0.01 ±5%
Vrms½ 434-II 1 V to 1000 V phase to neutral 0.1 V ± 1 % of nominal voltage
434-II and 435-II   0.1 V ±0.2% of nominal voltage
Vfund 434-II 1 V to 1000 V phase to neutral 0.1 V ± 0.5 % of nominal voltage
435-II   0.1 V ± 0.1 % of nominal voltage
Amps (accuracy excluding clamp accuracy)
Amps (AC + DC) i430-Flex 1x  5 A to 6000 A 1 A ±0.5% ±5 counts
i430-Flex 10x 0.5 A to 600 A 0.1 A ±0.5% ±5 counts
1mV/A 1x 5 A to 2000 A 1A ±0.5% ±5 counts
1mV/A 10x 0.5 A A to 200 A (AC only) 0.1 A ±0.5% ±5 counts
Apk i430-Flex 8400 Apk 1 Arms ±5%
1mV/A 5500 Apk 1 Arms ±5%
A Crest Factor (CF) 1 to 10 0.01 ±5%
Amps½ i430-Flex 1x 5 A to 6000 A 1 A ±1% ±10 counts
i430-Flex 10x 0.5 A to 600 A 0.1 A ±1% ±10 counts
1mV/A 1x 5 A to 2000 A 1 A ±1% ±10 counts
1mV/A 10x 0.5 A A to 200 A (AC only) 0.1 A ±1% ±10 counts
Afund i430-Flex 1x 5 A to 6000 A 1 A ±0.5% ±5 counts
i430-Flex 10x 0.5 A to 600 A 0.1 A ±0.5% ±5 counts
1mV/A 1x 5 A to 2000 A 1 A ±0.5% ±5 counts
1mV/A 10x 0.5 A A to 200 A (AC only) 0.1 A ±0.5% ±5 counts
Hz
Hz Fluke 434 @ 50 Hz Nominal 42.50 Hz to 57.50 Hz 0.01 Hz ±0.01 Hz
Fluke 434 @ 60 Hz Nominal 51.00 Hz to 69.00 Hz 0.01 Hz ±0.01 Hz
Fluke 435 @ 50 Hz Nominal 42.500 Hz to 57.500 Hz 0.001 Hz ±0.01 Hz
Fluke 435 @ 60 Hz Nominal 51.00 Hz to 69.00 Hz 0.001 Hz ±0.01 Hz
Power
Watts (VA, var) i430-Flex max 6000 MW 0.1 W to 1 MW ±1% ±10 counts
1 mV/A max 2000 MW 0.1 W to 1 MW ±1% ±10 counts
Power Factor (Cos j/DPF) 0 to 1 0.001 ±0.1% @ nominal load conditions
Energy
kWh (kVAh, kvarh) i430-Flex 10x Depends on clamp scaling and V nominal ±1% ±10 counts
Energy Loss i430-Flex 10x Depends on clamp scaling and V nominal ±1% ±10 counts Excluding line resistance accuracy
Harmonics
Harmonic Order (n) DC, 1 to 50 Grouping: Harmonic groups according to IEC 61000-4-7
Inter-Harmonic Order (n) OFF, 1 to 50 Grouping: Harmonic and Interharmonic subgroups according to IEC 61000-4-7
Volts % f 0.0% to 100% 0.1% ±0.1% ±n x 0.1%
r 0.0% to 100% 0.1% ±0.1% ±n x 0.4%
Absolute 0.0 to 1000 V 0.1 V ±5%1
THD 0.0% to 100% 0.1% ±2.5%
Amps % f 0.0% to 100% 0.1% ±0.1% ±n x 0.1%
r 0.0% to 100% 0.1% ±0.1% ±n x 0.4%
Absolute 0.0 to 600 A 0.1 A ±5% ±5 counts
THD 0.0% to 100% 0.1% ±2.5%
Watts % f or r 0.0% to 100% 0.1% ±n x 2%
Absolute Depends on clamp scaling and V nominal ±5% ±n x 2% ±10 counts
THD 0.0% to 100% 0.1% ±5%
Phase Angle -360° to +0° ±n x 1°
Flicker
Plt, Pst, Pst (1 min) Pinst 0.00 to 20.00 0.01 ±5%
Unbalance
Volts % 0.0% to 20.0% 0.1% ±0.1%
Amps % 0.0% to 20.0% 0.1% ±1%
Mains Signaling
Th reshold Levels Threshold, limits and signaling duration is programable for two signaling frequencies
Signaling Frequency 60 Hz to 3000 Hz 0.1 Hz  
Relative V % 0% to 100% 0.10% ±0.4%
Absolute V3s (3 second avg.) 0.0 V to 1000 V 0.1 V ±5% of nominal voltage
General Specifications
Case

Interested in this product?

Contact us via WhatsApp for more information, pricing, or to place an order.

Contact Us on WhatsApp
WhatsApp Chat